ITYS E
Strong Points
Best electrical protection
Robust and versatile
Function
Compact tower UPS system saves space in the operating environment.
Description
Please check with your local salespeople if the product is available in your country.
Technical data
ITYS E – UPS | |||||
---|---|---|---|---|---|
Sn | 1000 VA | 2000 VA | 3000 VA | 6000 VA | 10000 VA |
Pn | 800 W | 1600 W | 2400 W | 4800 W | 8000 W |
Input | |||||
---|---|---|---|---|---|
Model | 1000 VA | 2000 VA | 3000 VA | 6000 VA | 10000 VA |
Voltage | 230 V (1ph) 160÷300 V up to 110 V @ 60% load | ||||
Rated frequency | 50/60 Hz | ||||
Power factor | 0.99 |
Output | |||||
---|---|---|---|---|---|
Model | 1000 VA | 2000 VA | 3000 VA | 6000 VA | 10000 VA |
Rated voltage | 208 / 220 / 230 / 240 V | ||||
Voltage tolerance | ± 1% | ||||
Rated frequency | 50/60 Hz (46÷54 Hz / 56÷64 Hz) (in battery mode 50/60 ± 0.1 Hz) | ||||
Overload | Up to 130% for 1 minute | ||||
Crest factor | 3:1 |
Connections | |||||
---|---|---|---|---|---|
Model | 1000 VA | 2000 VA | 3000 VA | 6000 VA | 10000 VA |
IEC standard | 3 x IEC 320 | 4 x IEC 320 | 4 x IEC 320 + terminals | terminals | |
Universal standard | 2 sockets | 2 sockets | 2 sockets + terminals | terminals | |
Indian standard | 3 sockets | 4 sockets | 4 sockets + terminals | terminals |
Batteries | |||||
---|---|---|---|---|---|
Model | 1000 VA | 2000 VA | 3000 VA | 6000 VA | 10000 VA |
Type | sealed lead-acid maintenance free – expected life 3/5 years | ||||
Back-up time @75% of rated VA load pf 0.7 (Models with internal batteries) |
8 min | 9 min | |||
Voltage (Models without batteries) | 36 VDC | 96 VDC | 192 VDC | 240 VDC | |
Battery charger (Models without batteries) | Setting up to 6 A |
Communication | |||||
---|---|---|---|---|---|
Model | 1000 VA | 2000 VA | 3000 VA | 6000 VA | 10000 VA |
Interfaces | RS232 – USB | ||||
Local communication software | Local View |
Efficiency | |||||
---|---|---|---|---|---|
Model | 1000 VA | 2000 VA | 3000 VA | 6000 VA | 10000 VA |
Online mode | up to 90 % |
Environment | |||||
---|---|---|---|---|---|
Model | 1000 VA | 2000 VA | 3000 VA | 6000 VA | 10000 VA |
Ambient service temperature | 0 °C to +40 °C (15 °C to 25 °C for maximum battery lifetime) | ||||
Relative humidity | 0 to 95% without condensation | ||||
Maximum altitude | 1000 m without derating | ||||
Noise level at 1 m | < 55 dBA | < 59 dBA |
UPS CABINET (Models with internal batteries) | |||||
---|---|---|---|---|---|
Model | 1000 VA | 2000 VA | 3000 VA | 6000 VA | 10000 VA |
Dimensions W x D x H | 145 x 285 x 220 mm | 145 x 400 x 220 mm | 190 x 425 x 320 mm | 190 x 370 x 640 mm | 190 x 450 x 640 mm |
Weight | 10 kg | 17 kg | 28 kg | 60 kg | 75 kg |
Degree of protection | IP20 |
UPS CABINET (Models without batteries) | |||||
---|---|---|---|---|---|
Model | 1000 VA | 2000 VA | 3000 VA | 6000 VA | 10000 VA |
Dimensions W x D x H | 145 x 285 x 220 mm | 145 x 400 x 220 mm | 145 x 400 x 220 mm | 190 x 370 x 320 mm | 190 x 450 x 320 mm |
Weight | 5 kg | 7 kg | 8 kg | 12 kg | 16 kg |
Degree of protection | IP20 |
Standards | |||||
---|---|---|---|---|---|
Model | 1000 VA | 2000 VA | 3000 VA | 6000 VA | 10000 VA |
Safety(1) | EN 62040-1 | ||||
EMC(1) | EN 62040-2 | ||||
Product declaration(1) | CE | ||||
BIS certification | R-41030651 | R-41120790 |
(1) Models with IEC output sockets.